d) Curves, technical data, torsional information with the following as a minimum: i. Complete Generator Data Sheet (Attachment 2) ii. Generator capability (kW or KVA) vs. ambient temperature (F or °C) curve, including data points so Solar Turbines Incorporated can create a generator vs. turbinecapability curve. At a minimum, this data shall cover the temperature range as specified in the GPD. iii. Reactive capability curve iv. Short circuit decrement curve v. Generator and exciter saturation curves (only when First Article Tests are specified) vi. Generator efficiency vs. percent load (at 0.8 pf and 1.0 pf) curve vii. Bearing data as outlined in (Attachment 2) viii. Current Transformer data sheets and excitation curves ix. Lateral Analysis x. Vee Curve xi. Generator Impeller Fan Flow Curve: Static Pressure (in wg) vs. Airflow (cfm) including generator internal pressure loss. xii. Cooling Airflow Requirements: Minimum airflow required at low and high ambient conditions.