④ Verification of current transformer (CT) a. Dynamic stability verifi的简体中文翻译

④ Verification of current transform

④ Verification of current transformer (CT) a. Dynamic stability verification The dynamic stability current of the selected switchgear is 80kA, which is greater than the short-circuit thermal thermal stability current of the GIS substation 110KV system 20.08kA, so it meets the thermal stability requirements. b. Thermal stability verification The thermal stability current of the selected switchgear is 32kA, which is greater than the thermal stability current of the GIS substation 110kV system short circuit 20.08kA, so it meets the thermal stability requirements. ⑤. Busbar verification a. Ue = 1 10kV, I = 1250A> GIS substation maximum long-term working current Igmax = 262.432A b.110kV side busbar three-phase short-circuit steady-state current = 20.08 kA rated heat of the selected switchgear circuit breaker The stable current is 31.5 kA so it meets the requirements. Voltage transformer (PT), the arrester need not test its thermal stability and dynamic stability, so here without making correction experience. Selection of equipment (1). Rated voltage: Ue = 35kV (2). Rated current: le> Maximum long-term working current Igmax of GIS substation, ie (3). According to the above analysis, choose the KYN7-40.5 type armor of Xi’an High Voltage Switch Factory Removable indoor AC metal enclosed switchgear, the relevant parameters are shown in Table 4-2.
0/5000
源语言: -
目标语言: -
结果 (简体中文) 1: [复制]
复制成功!
④电流互感器(CT)<br>的验证a。动态稳定性验证<br>所选开关柜的动态稳定电流为80kA,大于GIS变电站110KV系统的短路热稳定电流20.08kA,因此符合热稳定要求。<br>b。热稳定性验证<br>所选开关设备的热稳定性电流为32kA,大于GIS变电站110kV系统短路20.08kA的热稳定性电流,因此符合热稳定性要求。<br>⑤。母线验证<br>a。Ue = 1 10kV,I = 1250A> GIS变电站最大长期工作电流Igmax = 262.432A<br>b.110kV侧母线三相短路稳态电流= <br>所选开关柜断路器的额定热量20.08 kA 稳定电流为31.5 kA,因此符合要求。<br>避雷器是电压互感器(PT),无需测试其热稳定性和动态稳定性,因此此处无需进行校正<br>。<br>设备的选择<br>(1)。额定电压:Ue = 35kV <br>(2)。额定电流:le> GIS变电站的最大长期工作电流Igmax,即<br><br>(3)。根据以上分析,选择西安高压开关厂可移动室内交流金属封闭开关柜的KYN7-40.5型铠装,其相关参数如表4-2所示。
正在翻译中..
结果 (简体中文) 2:[复制]
复制成功!
(4) 电流变压器(CT)的验证<br>a. 动态稳定性验证<br>所选开关机的动态稳定电流为80kA,大于GIS变电站110KV系统20.08kA的短路热稳定性电流,满足热稳定性要求。<br>b. 热稳定性验证<br>所选开关机的热稳定性电流为32kA,大于GIS变电站110kV系统短路20.08kA的热稳定性电流,满足热稳定性要求。<br>(5) 巴士验证<br>a. Ue = 1 10kV,I = 1250A+ GIS 变电站最大长期工作电流 Igmax = 262.432A<br>b.110kV 侧母线三相短路稳定状态电流 = 20.08 kA<br>所选开关设备断路器的额定热量 稳定电流为 31.5 kA,因此符合要求。<br>电压变压器(PT),抑制器无需测试其热稳定性和动态稳定性,所以在这里无需进行校正<br>经验。<br>设备选择<br>(1) 额定电压:Ue = 35kV<br>(2) 额定电流:le= GIS 变电站的最大长期工作电流 Igmax,即<br><br>(3)根据上述分析,选择KYN7-40.5型装甲的西安高压开关厂可拆卸室内交流金属封闭开关设备,相关参数如表4-2所示。
正在翻译中..
结果 (简体中文) 3:[复制]
复制成功!
④ 电流互感器(CT)校验<br>a、 动态稳定性验证<br>所选开关柜的动稳定电流为80kA,大于GIS变电站110KV系统短路热稳定电流20.08kA,满足热稳定要求。<br>b、 热稳定性验证<br>所选开关柜热稳定电流为32kA,大于GIS变电站110kV系统短路热稳定电流20.08kA,满足热稳定要求。<br>⑤. 母线校验<br>a、 Ue=1 10kV,I=1250A>GIS变电站最大长期工作电流Igmax=262.432A<br>b、 110kV侧母线三相短路稳态电流=20.08kA<br>所选开关柜断路器的额定热稳定电流为31.5kA,满足要求。<br>电压互感器(PT),避雷器不需要测试其热稳定性和动态稳定性,所以这里不做校正<br>经验。<br>设备选择<br>(1) 是的。额定电压:Ue=35kV<br>(2) 是的。额定电流:le>GIS变电站最大长期工作电流Igmax,即<br>(3) 是的。根据以上分析,选用西安高压开关厂KYN7-40.5型铠装可移动式室内交流金属封闭开关设备,相关参数见表4-2。
正在翻译中..
 
其它语言
本翻译工具支持: 世界语, 丹麦语, 乌克兰语, 乌兹别克语, 乌尔都语, 亚美尼亚语, 伊博语, 俄语, 保加利亚语, 信德语, 修纳语, 僧伽罗语, 克林贡语, 克罗地亚语, 冰岛语, 加利西亚语, 加泰罗尼亚语, 匈牙利语, 南非祖鲁语, 南非科萨语, 卡纳达语, 卢旺达语, 卢森堡语, 印地语, 印尼巽他语, 印尼爪哇语, 印尼语, 古吉拉特语, 吉尔吉斯语, 哈萨克语, 土库曼语, 土耳其语, 塔吉克语, 塞尔维亚语, 塞索托语, 夏威夷语, 奥利亚语, 威尔士语, 孟加拉语, 宿务语, 尼泊尔语, 巴斯克语, 布尔语(南非荷兰语), 希伯来语, 希腊语, 库尔德语, 弗里西语, 德语, 意大利语, 意第绪语, 拉丁语, 拉脱维亚语, 挪威语, 捷克语, 斯洛伐克语, 斯洛文尼亚语, 斯瓦希里语, 旁遮普语, 日语, 普什图语, 格鲁吉亚语, 毛利语, 法语, 波兰语, 波斯尼亚语, 波斯语, 泰卢固语, 泰米尔语, 泰语, 海地克里奥尔语, 爱尔兰语, 爱沙尼亚语, 瑞典语, 白俄罗斯语, 科西嘉语, 立陶宛语, 简体中文, 索马里语, 繁体中文, 约鲁巴语, 维吾尔语, 缅甸语, 罗马尼亚语, 老挝语, 自动识别, 芬兰语, 苏格兰盖尔语, 苗语, 英语, 荷兰语, 菲律宾语, 萨摩亚语, 葡萄牙语, 蒙古语, 西班牙语, 豪萨语, 越南语, 阿塞拜疆语, 阿姆哈拉语, 阿尔巴尼亚语, 阿拉伯语, 鞑靼语, 韩语, 马其顿语, 马尔加什语, 马拉地语, 马拉雅拉姆语, 马来语, 马耳他语, 高棉语, 齐切瓦语, 等语言的翻译.

Copyright ©2024 I Love Translation. All reserved.

E-mail: