3.4.10 Low Temperature Operation Of Generators - The turbine has higher output power capabilities at lower ambient temperatures. Enclosed ODP generators will see, on average, 2.8°C (5.0°F) warmer air than the turbine. The generator output shall exceed the turbine output in the ambient temperature range specified in the GPD at a 0.8 power factor. Care shall be taken to size the generator appropriately when turbine air inlet chilling / evaporative cooling is specified in the GPD.