Proscenium Walls – A stage shall be completely separated from the auditorium by a proscenium wall of not less than two-hour incombustible construction. The proscenium wall shall extend not less than 1.20 meters above the roof over the auditorium. Proscenium walls may have, in addition to the main proscenium openings, one (1) opening at the orchestra pit level and not more than two (2) openings at the stage floor level, each of which shall be not more than 2.00 sq. meters in area. All openings in the proscenium wall of stage shall be protected by a fire assembly having a one and one-half - hour fire-resistive rating. The proscenium opening, which shall be the main opening for viewing performances, shall be provided with a self-closing fire-resistive curtain as specified in the Code.