.3MaterialsThe cables manufactured shall also be a product regularly manufactured by the Supplier.The cable drum radius should not be less than 125% of the minimum bending radius of the cables.Cables shall be manufactured in one continuous length as per ordered drum length. Splices in conductors, insulation or sheaths are not acceptable Cable conductors shall be made of class B tinned concentric stranded, continuous copper conductor made up from fully annealed round copper wires free from imperfections in accordance to IEC 60228 class 2