According to Article 26.10.5-4 of the "Practical Heating and Air Conditioning Design Manual", the water replenishment of the cooling tower includes wind drifting loss, evaporation loss, blowdown loss and leakage loss. Generally, 1% to 2% of the cooling water is used as water replenishment the amount. For systems without a water collection tank, water should be replenished at the cooling tower chassis, and for systems with a water collection tank, water should be replenished at the water collection tank. Therefore, the amount of water supplied to the cooling tower is 71.64 × 1% = 0.71m³ / h, and the amount of water supplied to the cooling tower is 71.64 + 0.72 = 72.36m³ / h.