Please find the following comments for your follow-up as: Please submit the light specification/catalogue;The proposed power cable shall be the same as the existing ones, which is 3P 16mm2 + N 16 mm2;All proposed cabling shall be equipped with amour;Although the lighting poles installation is considered to be temporary, the installation shall be considered as the requirement of a permanent installation for electrical safety reason. For example, earthing/grounding and the UG galvanized steel pipes shall be provided;Megger Test and other related cable test(s) shall be provided with calibration certificates of testing equipment.