enclosure appropriate for the installation and as specified. 1.08 Downstream (outgoing cables from motor control center/motor control panel) wires, cables, control wires and connections between motor control centers/panels and disconnect switches or motors; cable trays, conduits are measured separately under the respective section of Division 26 and shall not be deemed included with the motor control centers/panels. 262500 ENCLOSED BUS ASSEMBLIES 1. Generally 1.01 Each kind of enclosed bus assemblies is given separately, stating the rating, type and method of installation. 1.02 Enclosed bus assemblies are given in linear metres, measured the net length. 1.03 Tap-off units are given separately, stating the rating and type. 1.04 Tap-off units are enumerated. 1.05 Rates for enclosed bus assemblies are deemed to include the costs of: mounting fittings, hangers and supports, jointing between sections, expansion joints, elbows, bends, tees, reducers and the like, and all related accessories, cable end boxes, transformer flange connections, switchboard flange connections, end plates and the like, connection units to equipment/boards including mounting fittings, termination to equipment/boards and bus assemblies and all related accessories, fire sealant where passing through fire rated wall or floor, earthing system, as applicable. 262726 WIRING DEVICES 1. Generally