LCP Description 1 No. incoming 16 Amp.(adjust) TP, MCCB, 18 kA 2 Nos. outgoing 16 Amp. TP MCCBs, 18 kA 1 No, spare 16/Vnp. TP MCCBs, 18 kA 2 Nos. 32 Amp. magnetic contactor, AC-3 1 No. spare 32 Amp. magnetic contactor, AC-3 3 Nos, photo-electric switches a) 1 No. ammeters 0-40 Amp., with selector switch (04 position) and CT of 50/5 Amp b) 09 Nos. indication Sights c) 1 No. voltmeter with fuse and 7 position selector switch. d) 3 Ph, N & Earth copper busbar e) Internal wiring & line-up terminals etc. f) Brass cable glands/accessories g) 3 Nos. Auto-Manual-OFF (3 position switches for operation in auto (with photocell) and normal (manual mode- photocell overide) h) Panel steel grid painted alongwith locking arrangement i) IP =44/54 panel shall be weather proof, dust proof wiUi studded and shade arrangement on top.