The enclosure shall provide a minimum of two conductor entry openings so that the Class 2, Class 3, and power-limited fire protection circuit conductors are segregated from electric light, power, Class 1 and nonpower-limited fire protection circuit conductors. The installation document shall completely detail the entry routing of all conductors into the enclosure