• The supply fan power relationships in Figure 10 suggest the VAVR system's horsepower is reduced in proportion to the cube of the airflow reduction. The only way this can be achieved is for the fan to "ride the system curve," meaning no dampers ever move. This would never happen in an actual system in a building. If the overall fan airflow reduction were 40%, yet one zone still required 80% of its design airflow, the static pressure requirement of that zone would limit the system static pressure reset. Applying the fan laws to that specific zone, the static pressure requirement for that terminal could only be reduced by 36%. Using Table 1 data, a 40% system airflow reduction combined with a 36% reduction in the fan static pressure would result in a fan break horse power变风量再热与主动冷却梁和DOA
0/5000
源语言: -
目标语言: -
结果 (简体中文) 1: [复制]
复制成功!
•图10中的电源风扇功率关系表明VAVR系统的马力与气流减少的立方成正比。唯一可以实现的方法是使风扇“顺着系统曲线”,这意味着没有风门移动。在建筑物的实际系统中永远不会发生这种情况。如果风扇总气流减少了40%,而一个区域仍需要其设计气流的80%,则该区域的静压要求将限制系统静压的复位。<br>将风扇定律应用于该特定区域,该终端的静压要求只能降低36%。使用表1的数据,系统气流减少40%,风扇静压减少36%,将导致风扇断马力<br>变风量再热与主动冷却梁和DOA
正在翻译中..
结果 (简体中文) 2:[复制]
复制成功!
• 图 10 中的电源风扇功率关系表明 VAVR 系统的马力与气流减少的立方体成正比。唯一可以实现这一点的方法是风扇"骑系统曲线",这意味着没有阻尼器永远不会移动。这在建筑物的实际系统中永远不会发生。如果风扇气流总体减少 40%,但一个区域仍需要其设计气流的 80%,则该区域的静态压力要求将限制系统静态压力重置。<br>将风扇法应用于该特定区域,该终端的静态压力要求只能降低 36%。使用表 1 数据,40% 的系统气流减少,加上风扇静态压力减少 36%,将导致风扇断马功率<br>可攻击性多特性多阿多
正在翻译中..
结果 (简体中文) 3:[复制]
复制成功!
• The supply fan power relationships in Figure 10 suggest the VAVR system's horsepower is reduced in proportion to the cube of the airflow reduction. The only way this can be achieved is for the fan to "ride the system curve," meaning no dampers ever move. This would never happen in an actual system in a building. If the overall fan airflow reduction were 40%, yet one zone still required 80% of its design airflow, the static pressure requirement of that zone would limit the system static pressure reset. Applying the fan laws to that specific zone, the static pressure requirement for that terminal could only be reduced by 36%. Using Table 1 data, a 40% system airflow reduction combined with a 36% reduction in the fan static pressure would result in a fan break horse power变风量再热与主动冷却梁和DOA<br>
正在翻译中..
 
其它语言
本翻译工具支持: 世界语, 丹麦语, 乌克兰语, 乌兹别克语, 乌尔都语, 亚美尼亚语, 伊博语, 俄语, 保加利亚语, 信德语, 修纳语, 僧伽罗语, 克林贡语, 克罗地亚语, 冰岛语, 加利西亚语, 加泰罗尼亚语, 匈牙利语, 南非祖鲁语, 南非科萨语, 卡纳达语, 卢旺达语, 卢森堡语, 印地语, 印尼巽他语, 印尼爪哇语, 印尼语, 古吉拉特语, 吉尔吉斯语, 哈萨克语, 土库曼语, 土耳其语, 塔吉克语, 塞尔维亚语, 塞索托语, 夏威夷语, 奥利亚语, 威尔士语, 孟加拉语, 宿务语, 尼泊尔语, 巴斯克语, 布尔语(南非荷兰语), 希伯来语, 希腊语, 库尔德语, 弗里西语, 德语, 意大利语, 意第绪语, 拉丁语, 拉脱维亚语, 挪威语, 捷克语, 斯洛伐克语, 斯洛文尼亚语, 斯瓦希里语, 旁遮普语, 日语, 普什图语, 格鲁吉亚语, 毛利语, 法语, 波兰语, 波斯尼亚语, 波斯语, 泰卢固语, 泰米尔语, 泰语, 海地克里奥尔语, 爱尔兰语, 爱沙尼亚语, 瑞典语, 白俄罗斯语, 科西嘉语, 立陶宛语, 简体中文, 索马里语, 繁体中文, 约鲁巴语, 维吾尔语, 缅甸语, 罗马尼亚语, 老挝语, 自动识别, 芬兰语, 苏格兰盖尔语, 苗语, 英语, 荷兰语, 菲律宾语, 萨摩亚语, 葡萄牙语, 蒙古语, 西班牙语, 豪萨语, 越南语, 阿塞拜疆语, 阿姆哈拉语, 阿尔巴尼亚语, 阿拉伯语, 鞑靼语, 韩语, 马其顿语, 马尔加什语, 马拉地语, 马拉雅拉姆语, 马来语, 马耳他语, 高棉语, 齐切瓦语, 等语言的翻译.

Copyright ©2024 I Love Translation. All reserved.

E-mail: