a) Certified drawings which include shaft details, WK2 for rotating parts, outline dimensions, weights, installation details, airflow directions, center of gravity, static load, support pad details, dynamic (short circuit) load, torsional data, nameplate data, terminal box details, thermal growth values/directions for alignment purposes, etc., to permit Solar to evaluate packaging needs. b) Certified wiring connections and schematics diagrams for all electrical circuitry including alarm and shutdown set points for vibration and temperature detection. c) Generator and exciter acceptance test reports (date of submittal as specified on the purchase order). See paragraphs 4.3.1 and 4.3.2.