According to Article 1 of article 7.2.11 of code for design of heating, ventilation and air conditioning of civil buildings (gb50736-2012), when the terminal equipment is equipped with automatic temperature control device, the summer cooling load of the air conditioning system is determined according to the comprehensive maximum hourly cooling load of each air conditioning area served, and the fan panel with automatic temperature control device is used at the end of the air conditioning system in this design Therefore, according to the above regulations, the cooling load of the system shall be determined according to the comprehensive maximum hourly cooling load of each air conditioning area served. And because the design of the fresh air system adopts the fresh air unit, the fresh air load should be added to the comprehensive cooling load of the system as the total cooling load value of the system.<br>