Ic GIS substation maximum long-term working current Igmax 262.432A <br>b. Dynamic stability verification <br>110 kV side bus three-phase short-circuit impulse current Ia = 51.204 kA <br>Rated dynamic stable current of selected switchgear disconnector I = 80 kA <br>I GIS substation maximum long-term operation Current Igmax = 262.432A <br>b. Dynamic stability verification <br>110 kV side bus three-phase short-circuit impulse current Ich = 51.204 kA <br>Rated dynamic stable current of the selected switchgear grounding switch I = 80 kA <br>Ich GIS substation maximum long-term working current Igmax = 262.432A <br>b. 110kV side bus three-phase short-circuit steady-state current = 20.08 kA <br>The rated thermal stability current of the selected switchgear circuit breaker is 31.5 kA, so it meets the requirements. <br>Voltage transformer (PT), the arrester need not test its thermal stability and dynamic stability, so here without making correction <br>experience. <br>Selection of equipment <br>(1). Rated voltage: Ue = 35kV <br>(2). Rated current: le> Maximum long-term working current Igmax of GIS substation, namely <br><br>(3). Based on the above analysis, choose the KYN7-40.5 type armor of Xi’an High Voltage Switchgear Factory Removable indoor AC metal enclosed switchgear, the relevant parameters are shown in Table 4-2. <br>Table 4-2 KYN7-40. Main parameter table of type 5 armored removable indoor AC metal-enclosed switchgear [17] <br>Project unit parameters <br>Rated voltage kV 40.5 <br>Main bus rated current A 1600 <br>Rated thermal stability current kA 20 <br>Rated dynamic stability Current kA 50 <br>Power frequency withstand voltage kV 95<br>Lightning impulse withstand voltage kV 185 <br><br>(4). Check <br>①. Ue = 35kV, I = 1600A> GIS substation maximum long-term working current Igmax = 824.786A <br>②. Dynamic stability check <br>35 kV side bus three-phase short-circuit impulse current lch = <br>Rated dynamic stable current of 10.608 kA selected switchgear I = 50 kA <br>IchGIS substation maximum long-term working current Igmax = 4811.252A <br>②.②. Dynamic stability verification <br>10kV side bus three-phase short-circuit impact current Ich = 99.450 kA <br>selected switchgear Rated dynamic stable current I = 125 kA <br>Ia
正在翻译中..