6. Construction 6.1 Identification Mating components of a separable insulated connector shall be permanently (for example, ink stamped, branded, or molded in) and legibly identified with the following information: a) Manufacturer's identification 1) Company name or logo 2) Part identification 3) Date of manufacture b) Continuous current rating (when applicable) c) Maximum voltage rating 1) 200 A and 600 A deadbreak connectors: Identify with the maximum phase-to-ground voltage rating. 2) 200 A loadbreak connectors: Three-phase: Identify with the maximum phase-to-ground/phase-to-phase voltage rating. Single-phase: Identify with the maximum phase-to-ground voltage rating. d) Cable insulation diameter range (when applicable) e) Whether loadbreak or deadbreak (when applicable). In addition to the word “LOADBREAK,” elbows of loadbreak connectors shall have the following markings: 1) Connectors with a phase-to-ground voltage rating shall be identified with a removable white band from 13 mm to 32 mm (0.5 in to 1.25 in) wide, located on the cable entrance portion of the connector not less than 25 mm (1.00 in) from the cable entrance. The removable band shall be clearly visible from the normal operating position, and affixed to minimize its accidental dislodgment. 2) Connectors with both phase-to-ground and phase-to-phase voltage ratings shall be identified with a removable white band from 13 mm to 32 mm (0.5 in to 1.25 in) wide, having a centered black stripe 4.8 mm ± 1.6 mm (0.188 in ± 0.062 in) in width located on the cable entrance portion of the connector not less than 25 mm (1.00 in) from the cable entrance. The removable band shall be clearly visible from the normal operating position, and affixed to minimize its accidental dislodgment. f) Color-coding: In addition to the white bands of item e) of this subclause, 200 A loadbreak connectors may, at the option of the manufacturer, be identified by a color as specified in Table 3.