8.2.5 Transition of an intentional island from the Area EPSIf an intentional island that does not qualify as an exception under 6.4.2.1 or 6.5.2.1 disconnects from the Area EPS when the voltage and frequency of the Area EPS are within the Continuous Operation ranges defined in Clause 6, the conditions of 7.2.2, as applicable, shall be met.8.2.6 Reconnection of an intentional island to the Area EPSAn intentional island that has disconnected from the rest of the Area EPS may reconnect to the rest of the Area EPS when the conditions listed in 4.10 are met at the intentional island point of common coupling. When the intentional island reconnects to the Area EPS, the conditions of 4.10.4 shall be met.8.2.7 Adjustments to DER settingsWhen operating in an intentional Area EPS island, participating DER may have to adjust several control and protection settings. These alternate settings and ranges of allowable settings, including those specified in 8.2.7, shall be enabled only when the intentional Area EPS island is isolated from the Area EPS. In order to meet this requirement, adaptive protection and control settings may be required.For DER operating in an intentional Area EPS island, the following requirements apply: 5.2 (reactive power capability of the DER) and 5.3 (voltage and reactive power control) for all aggregate DER ratings.