At present, most of the multi-storey or high-rise residential buildings designed use the common riser system. In the design, the heating system and the common riser should be changed vertically according to the factors such as the hydraulic balance of the system, heat dissipation equipment, pressure bearing capacity and the characteristics of chemical pipes, and the problem of pipeline thermal compensation should be considered. However. In some designs, it is considered that the indoor laying is buried, and the thermal expansion of the common riser in the pipe well is ignored, so the expander is not set; Although some compensators are designed, the thermal expansion is not carefully checked to determine the position of the compensator; In other designs, fixed supports are installed at the upper and lower positions of the compensator, so that the compensator can not solve the problem of deformation and expansion of the pipeline due to thermal expansion, resulting in the cracking of the branch pipe due to the thermal expansion and expansion of the riser.<br>