04IS 1110: FLAME NEAR 04D 110 /04 F 110(ESD)CAUSE OF ACTION:1) Flame presence signaled by 04BS 1101A or 04BS 1101B or 04BS 1101CACTIONS:1) Shuts 04HV 1109 A/B (Teal to 04D 110)2) Shuts 04HV 1102 (04D 110 outlet)3) Stops 04P 110 A/B (Teal metering pumps)4) Board signaling of 04IS 1110 ON04IS 1110 is manually RESET by 04HS 1116 RESET (Local Board)Flame detector failure shall not be involved in the interlock.04IS 1111: FLAME NEAR 04P 110 A (ESD)CAUSE OF ACTION:1) Flame presence signaled by 04BS 1102ACTIONS:1) Shuts 04HV 1104 (04P 110A suction)2) Stops 04P 110 A (Teal metering pump)3) Shuts 04HV 1106 (04P 110A discharge)4) Board signaling of 04IS 1111 ON 04IS 1111 is manually RESET by 04HS 1117 RESETFlame detector failure shall not be involved in the interlock.