3.4.2 Section 3The power cables identified as “Section 3” in Figure 1 shall connect capacitor bank C(52)2 with MV1 and MV3 test cells. Their duty cycles shall be coordinated with the one of the above-mentioned bank and is defined as follows:• No. 20 tests, each one lasting 1s, in a period of 1 hourThe basic duty cycle shall be repeated eight times in one working day.3.5 Scope of SupplyThe supply shall include cables, terminations, brackets and cleats and all the accessories needed for the correct laying and exploiting of cables.For each cable link suitable margins in cable length shall be taken into account, considering curves, position in gallery, civil works tolerances and remnant at cable ends for terminations and eventual new terminations in case of fault on cable terminal.3.6 Completeness of supplyThe content of this technical specification is purely indicative; the Contractor has the responsibility of the supply of all the systems and components necessary to realize the requested service even if they are not clearly mentioned in the present document.All the drawings relevant to the supply shall be subjected to the prior approval by the Client, even if this shall not relieve the Supplier from the full responsibility of the supply.4 PERFORMANCEThe requirements of IEC Standards with respect to type tests, service and operation shall be applied to the specified power cable systems, as far as they are applicable to their ratings (see chapter 5).