The chilled water system adopts variable flow primary pump system and constant flow of chiller. According to the "Code for Design of Heating, Ventilation and Air Conditioning in Civil Buildings" (GB50736-2012): 8.5.8 When the variable flow primary pump system adopts the fixed flow mode of the chiller, an electric bypass regulating valve should be installed between the supply and return water channels of the system .