Power frequency withstand voltageThe test shall be carried out at the following locations:A. between the power terminal and the ground (enclosure);B. Between the output circuit terminal and the ground (housing);C. between the live parts and the enclosure made of insulating materials (or covered).The test should be sine wave, and the frequency allowed is between 45 Hz and 62 Hz. The test transformer should have enough capacity to keep the test voltage unaffected by leakage current. During type inspection, the applied power frequency test voltage at the beginning should not exceed 50% of the specified test voltage, and then the test voltage should rise to the specified value smoothly and keep it for 5s. During routine (ex-factory) inspection, it is allowed to apply the specified test voltage to the test site for 1s.Between the power supply terminal of the controller and the housing, and between the output circuit terminal and the housing, it should be able to withstand the specified test voltage specified in the following table, and 1.5 times of the test voltage specified in the following table should be applied between the live parts and the housing made of insulating materials (or covered), without breakdown or flashover.