NOTES:1. WORK THIS DRAWING WITH:A) ROOF SUBSTRUCTURE DETAILS DRAWING - ZE#F.3124B) INSTRUCTION FOR SITE INSTALLATIONC) RECOMMENDED INSPECTION AND SITE PLAN FOR SITE2. ALL DIMENSIONS SHALL BE CHECKED ON SITE3. PART LIST SHOWS COMPLETE MATERIAL REQUIRED FOR THE ROOF CLADDING INSULATION SYSTEM.4. MINERAL WOOL MAT SHALL BE INSTALLED LAYER BY LAYER IN STAGGERED WAY.5. MINERAL WOOL MAT SHALL BE CUT-OUT AT NOZZLE AND EXTERNAL ATTACHEMENT AREAS AND COVERED SO NO GAP ISALLOWED.6. MINERAL WOOL MAT SHALL BE CUT AT WEB AND FIXED WITH SS WIRE ON THE WEB NOT TO SLIDE DOWN THE TANK ROOF.7. ROOF CLADDING SHALL START FROM OUTER EDGE AND SHALL PROCEED TO TANK CENTER TO AVOID EXCESSIVE WALKING ONMINERAL WOOL MAT.8. EACH EDGE CLADDING (RI-32) SHALL BE SCREWED ONLY TO ONE ROOF CLADDING (RI-41) AND NOT TO ROOF SUBSTRUCTURE.9. BEND 50MM STANDING SEAM ON ROOF CLADDING SHEETS RI-41 TO RI-46 AS SHOWN.10. THE STANDING SEAM IS TO CLOSE WITH ROOF CLADDING COVER PROFILE (RI-31) AND SECURED WITH SELF-DRILLING SS SCREW.11. THE SEAMS IN RADIAL DIRECTION ARE TO EXECUTE IN ROOF TILE MANNER TO AVOID THE INGRESS OF MOISTURE.