1.The Foundry Control Room layout has been modified, so the new positions of the cabinets indicated in your attached drawing are appropriate.2. The LCC-4 cable entry is from top, not for bottom. You can’t use a 400x400 hole as in your attached drawing. If you want, you can move the LCC-4 from the Control Room to the MCC Room downstairs (and the instrument cable tray shall coming into the MCC room too).3. Attached sketches are showing the foundations, marked in blue color, as per your design 900 x 3681 x 400 (H). We do not suggest this solution for the following: ·It’s necessary to review the two walkways (refer to drawing C045A001) and to foresee an intermediate step at a height of +200 for both the walkways·Maintenance on the roller side would be difficult because of these foundations.·Indicated load is now +15 ton each plinth. For the loads of the plinths, please refer to load list, doc. W000BE01 rev. 6