Tests shall be conducted in accordance with ANSI C119.4. A 750 kcmil aluminum conductor shall be used for 600 A connectors. The test shall be made without insulation on the conductor or current-carrying parts of the connector to avoid any deterioration of the insulation that may otherwise occur at the maximum temperature of this test. The conductor system shall meet the requirements given for Class A connectors in ANSI C119.4.