11.8 Protective systems11.8.1 LV machines larger than 100 kWLV machines which larger than 100 kW, shall be provided with embedded temperature detectors in the stator windings.At least six detectors shall be installed, two for each stator phase.The detectors shall be PT-100 Platinum resistance elements to IEC 60751.