According to Article 2 of article 7.3.19 of the civil code, the fresh air volume of the air conditioning area shall be determined according to the sum of the fresh air volume required by the fresh air dehumidification, the fresh air volume required to maintain the air pressure of the air conditioning area, the compensation exhaust air volume and the maximum fresh air volume required by the personnel; The room has a small amount of dehumidification, and the dehumidification is carried out by the fan coil. Therefore, the new air volume is selected according to the larger value of the sum of the fresh air volume required to maintain the air pressure in the air conditioning area, the compensation exhaust air volume and the fresh air volume required by the personnel.<br>According to Article - of 3.0.6 of the civil code, the fresh air volume of the office and the rest room is determined to be 30m / h for each person, and that of the lobby and the four seasons hall is determined to be 10m / h for each person. According to Article 8.3 of page 19 of the design manual, maintain the indoor positive pressure of 10Pa, the required air change times are 1.2 times / h, and the required air change times for the toilet are 3 times / h.