6.2 Pass/fail criteria An EUT is considered to comply with the requirements for islanding protection when each case of recorded run-on time is less than 2 s or meets the requirements of local codes. 7 Documentation At a minimum, the following information shall be recorded and maintained in the test report. a) Specifications of EUT. Table 8 provides an example of the type of information that should be provided. b) Measurement results. Table 9 provides an example of the type of information that should be provided. Actual measured values should be recorded. c) Block diagram of test circuit. d) Specifications of the test and measurement equipment. Table 10 provides an example of the type of information that should be provided. e) Any test configuration or procedure details such as methods of achieving specified load and EUT output conditions. f) Any additional information required by the testing laboratory's accreditation. g) Specify the evaluation criterion from 6.2 that was utilized to determine if the product passed or failed the test. Table 8 – Specification of the EUT provided by the manufacturer (example)