When the water consumption is large, the water pressure decreases, the frequency of the drive output increases, when the frequency of the drive operation reaches the upper limit, and stabilizes 10s operation, if the pipe network pressure is lower than the water pressure setting value at this time, increase the No. 2 pump. Under the logical control of PLC, the electromagnetic switch connecting the No. 1 pump motor to the drive is disconnected, the No. 1 pump motor is switched to the frequency operation, and the inverter is connected to the No. 2 pump motor, so that the No. 2 pump motor is operating in the speed control state.<br>When the water consumption is low, the water pressure increases, the frequency of the inverter output decreases, enters the pump reduction process, the pump motor speed decreases, when the frequency of the drive reaches the lower limit, and stabilizes 10s operation, if the pipe network pressure is higher than the water pressure setting, the drive control pump is stopped. If pump No. 1 is running at frequency, switch pump No. 1 from frequency to variable frequency.