The high and low voltage distribution cabinets designed in this design are selected as follows:Jyn-35,112 is available for voltage transformers on 35kV lines.Jyn-35,43 can be used for current transformers on 35kV line.Jyn2-10 can be selected for the 6kV outgoing current transformer on the low-voltage side of the 35kV main transformer.Pgl2-05 can be selected for the 380V outgoing current transformer on the low-voltage side of the 6kV transformer.GG1A(F)-54 can be selected for the voltage transformer on the 6kV bus.