The automatic control ——— put the control selection key on the fire control controller in the "automatic" position. When the fire detector in the protected area sends a fire signal, the alarm control panel automatically emits a sound and light alarm, and at the same time issues a linkage command, the interlocking equipment (e.g. off ventilation and air conditioning, fire curtain door, etc.), after a pre-set 30-second delay time, the output startfire system signal, so that the corresponding protected area electromagnetic ally gas bottle group open, After the start of the gas release to open the corresponding selection valve and fire extinguishing agent storage bottle, release the fire extinguishing agent, the implementation of the fire extinguishing.<br>The manual control ——— place the control selection key on the fire control controller in the "manual" position. When the fire detector in the protected area sends a fire signal, the alarm control panel will automatically issue a sound and light alarm, and at the same time issue a linkage command, off the relevant equipment (such as closing ventilation and air conditioning, fire curtain door, etc.), but will not output the start of the fire extinguishing system signal, at this time need to be confirmed by the duty personnel, press the manual button on the fire control controller, Or the emergency start button outside the protected area, you can open the drive gas bottle set and fire extinguishing agent storage bottle according to the automatic procedure, release the fire extinguishing agent, the implementation of the fire extinguishing.