3. For Department Store Operators ONLYa. Typical ventilation and air-conditioning will be provided through the mall common area HVAC system.b. Additional ventilation shall be provided by the Operator at Operator’s cost for special shops, such as food, cafe or odor producing shops, as per Owner’s or Manager’s approval.5.11 Permanent Power Supply and Chilled Water Supply1. Application for Permanent Power Supplya. Self insulation resistance test shall be completed and report shall be attached.b. MCB unit shall all be opened and MCB board shall be locked with photo provided.c. MCB board schematic showing the circuitry shall be included.d. The Operator should fill in the attached application form (Appendix N) with documents attached and submit to the Owner and the Manager at 7 days in advance.e. After approved by the Owner and the Manager, a joint site inspection would be required if any to ensure the electrical safety before DSC power on.2. Application for Permanent Chilled Water Supplya. Water sample shall be collected from the flushing and a page of photo record showing the water sample quality (color) shall be attached for the proof.b. The Operator should fill in the attached application form (Appendix O) with photo and pressure test report included and submit to the Owner and the Manager at 7 days in advance.c. After approved by the Owner and the Manager, the Owner and the Manager will inform DSC for the chilled water supply