Generally, the three-phase short-circuit current is the largest. When the short-circuit point occurs near the generator, the two-phase short-circuit current may be greater than the three-phase short-circuit current; when the short-circuit point is near the neutral grounded transformer, the single-phase short-circuit current may also be greater than the three-phase short-circuit current.<br>1. First, calculate the transfer reactance from each power supply to the short-circuit point (unit value representation under a reference capacity as the reference value);<br>2. Calculated reactance converted to the reference value of each power supply capacity;<br>3. The capacity of each power supply divided by each calculated reactance is the short-circuit current of each power supply at the short-circuit point;<br>4. The sum of the above short-circuit currents is the total short-circuit current (sub transient value).<br>The calculation of three-phase short-circuit current is a necessary work in the planning, design and operation of power system. At present, the problem of three-phase short-circuit current exceeding the standard has become a key problem that puzzles the operation of many domestic power grids. However, in the calculation of three-phase short-circuit current, the calculation methods used in each design, operation and research part are different, which may cause the difference of short-circuit current calculation conclusion, the difference of short-circuit current exceeding standard judgment and the difference of short-circuit current limiting measures.<br>If the calculation result of short-circuit current is conservative, it may cause unnecessary investment waste; if it is optimistic, it will cause disastrous hidden danger to the safe and stable operation of the system. Therefore, based on the deep research of short-circuit current calculation standard, this paper compares the influence of different short-circuit current calculation conditions on the short-circuit current calculation conclusion, in order to provide more practical methods and ideas for the calculation and limitation of short-circuit current in power grid.<br>
正在翻译中..