3.4.4 Voltage Transients - Sudden application or rejection of load when the generator is operating at rated voltage and frequency shall result in a maximum voltage excursion not to exceed the limits shown on Table 6. Values of voltage excursions with loads in excess of the nameplate rating shall be made available, if requested.