110kV overhead lines should use steel-cored aluminum wire, and coastal areas and areas with corrosive gas should use anti-corrosion-type steel-cored aluminum wire [11]. In the case of reasonable technology and economy, the improvement of overhead lines should consider the use of new conductor materials. The conductor cross-section of the overhead lines should be selected according to the needs of long and short power supply capacity, according to the economic current density of the conductor, and according to the requirements of the limit transmission capacity under the failure mode Proofread. Generally, 2-3 specifications can be selected in the same area. Commonly, there are 300mm2, 400mm2 and <br>110kV power cables. If there are no special requirements, copper-core cables should be used, and single-core structures can be used. It is preferred to use cross-linked polyethylene for insulation. The cable interface should be selected according to the distance limit transmission capacity of the line. The medium voltage distribution network uses a 10kV voltage level. When a 110kV single main transformer adopts 50MVA, the 110kV cable section can be 630mm2, 800mm2.