We’ve received the electrical documents for PK 460. Thank you for sending to us.Our comments are as follows:- The incoming line has also neutral phase which is not in accordance with our specification E001D460 (please refer to TRS n. 60). In MCC-2 the feeder for PK 460 is three-phase without neutral. It means it will be necessary to take out the conductor of the neutral phase and to add a dedicated auxiliary transformer for the users at 220V of the PK 460 cabinet;- Please inform us if the touch panel is Siemens as the PLC;- PLC internal of the cabinet is acceptable;- Communication with our PLC installed in LCC-2 will be hardwired as per specification E001D460