Location – In Group H and I Occupancies, outlets shall be located as follows: one (1) on each side of the stage, one (1) at the rear of the auditorium, and one (1) at the rear of the balcony. Where occupant loads are less than five hundred (500) the above requirements may be waived; Provided, that portable fire extinguishers of appropriate capacity and type are installed within easy access from the said locations. In Group B, C, D, E, F and G Occupancies, the location of all interior wet standpipes shall be in accordance with the requirement for dry standpipes; Provided, that at least one (1) standpipe is installed to cover not more than 650 sq. meters