The 2.4L type dry-wet combination cooling tower operation controls <br>the cooling water temperature control steps of the cooling tower as follows: <br>1) Fully close the shutters of the wet cooling section, fully open the shutters of the dry cooling section, turn on the fan, and the circulating water passes through the heat exchange tube bundle to cool and then passes through the spray The shower layer goes directly into the pool. <br>2) As the ambient temperature continues to rise, the regulation is as follows: gradually open the louvers in the wet-cooling section, and gradually close the louvers in the dry-cooling section when the louvers in the wet-cooling section are fully opened. When the louvers in the dry-cooling section are fully closed, the maximum cooling capacity of the cooling tower is reached.